DMIII MULTITEST
EN-57
7.6. "POWER" FUNCTION
This function permits to display in real time the RMS value of AC/DC voltage, the peak and
ThdV value of the 3 phase voltages, the waveform of the 3 phase voltages, the RMS value
of AC/DC currents, the peak and Thdl of the 3 phase currents and the waveform of the 3
phase currents. Furthermore, the instrument calculates and displays the value of phase
and total active powers, the value of phase and total reactive and capacitive powers, the
value of phase and total power factors and cos.
7.6.1. Symbols
The position POWER has two working modes:
METER
WAVE
For voltage and current harmonics see paragraphs 7.4.3 and 7.5.3 respectively.
These modes will be described in detail in the next paragraphs.
The symbols used are described below:
RMS value of voltage (phase 1, phase 2, phase 3 respectively)
RMS value of phase to phase voltages
"123" correct
"132" inverted
"023" null voltage on black wire
"103" null voltage on red wire
"120" null voltage on blue wire
"100" null voltages on red and blue wires
"020" null voltages on black and blue wires
"003" null voltages on black and red wires
RMS value of current (phase 1, phase 2, phase 3 respectively)
RMS value of current of neutral
Values of active power (total, phase 1, phase 2, phase 3 respectively)
(only for 3-wire measurement) value of power measured by Wattmeter 1-2 and 3-2
respectively
Values of reactive power (total, phase 1, phase 2, phase 3 respectively)
(only for 3-wire measurement) Value of power measured by VAR meter Va1-2 and
3-2 respectively
Values of apparent power (total, phase 1, phase 2, phase 3 respectively)
(only for 3-wire measurement) Value of power measured by VA meter Va1-2 and 3-
2 respectively
Values of power factors (total, phase 1, phase 2, phase 3 respectively)
Value of the cos (total, phase 1, phase 2, phase 3 respectively)
Values of total active energy and active power on demand respectively
Values of total apparent energy and apparent power on demand respectively
Tab. 3: Symbols used in the POWER function
The symbols "i" and "c" stand for reactive powers (Q), power factors (Pf) and cos (dpf),
inductive and capacitive respectively.