At the end of the test
the instrument emits a
double beep indicating
that the test is
correctly terminated
and displays the values
to the right.
EARTH 05.06.01
Ground Resistance value
expressed in .
0.77
Vd= 1V
Test:04
RAVG=0.74
3-W
Voltage value of electrical
noise
Number of Test
Average Value of Ground
Resistance calculated over
the Number of Test
displayed.
FUNC
CLR
"3 Point" Working mode
4. The instrument will show automatically the average value of the Ground resistance
calculate over the tests performed. Press F2 to RESET this value and the number of
Test.
This result can be stored by pressing the SAVE key twice (refer to paragraph 9.1).