Amprobe DMIII-Multitest Power-Quality-Recorder Instrukcja Użytkownika Strona 19

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 104
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 18
AMPROBE
DMIII MULTITEST
EN-17
6.1.3. Results of "AUTO" mode
At the end of the test, if
the average resistance
value Ravg is lower
than 5 the instrument
emits a double sound
signal indicating the
positive outcome of
the test and displays a
screen similar to the
screen to the right.
LOW 05.06.01
Average resistance value
(Ravg)
1.05
R+ R-
1.07 1.03
219mA 219mA
AUTO 0.11
Resistance values and
corresponding test currents
obtained after exchanging
the polarities of test leads
FUNC
CAL
The displayed result can be stored by pressing the SAVE key twice (refer to
paragraph 9.1).
6.1.4. Results of "RT+" and "RT-" modes
If a resistance value
RT+ or RT- lower than
5 is detected, the
instrument emits a
double sound signal
indicating the positive
outcome of the test
displays a screen similar
to the screen to the
right.
LOW 05.06.01
Max Resistance value of
R+ or R-.
1.07
219mA
RT+ 0.11 TIME: 10s
Test current
Duration of the Test
FUNC
CAL
Note: We recommend the use of alligator clips and to assure the alligator clips make good
contact with the conductor under test. Indeed, in this test the instrument gives as a
final result the maximum measured value of R+ or R- and using test leads instead of
alligator clips could give you faulty results due to faulty contact between the test leads
and conductor under test
The displayed result can be stored by pressing the SAVE key twice (refer to
paragraph 9.1).
Przeglądanie stron 18
1 2 ... 14 15 16 17 18 19 20 21 22 23 24 ... 103 104

Komentarze do niniejszej Instrukcji

Brak uwag