3736
Surface Probe
For detailed specifications go to www.Amprobe.eu
FUNCTION RANGE ACCURACY
Air Velocity m/s
0.40 m to 25.00 m/s ± 2 % of full scale
ft/min
125 ft to 4900 ft/min ± 2 % of full scale
Air Flow cm/s
0.01 m to 99.99 m3/sec 0 to 9.999 m
cf/m
1 ft to 9999 ft3/min 0 to 9.999 ft
Air Temp. °C
0 °C to 50 °C ± 0.8 °C
Temperature
B Triple display of T1, T2, T1 - T2, plus
relative time stamp
B Dual inputs-for easy super-heat and
sub-cool temperature measurements
B Deluxe hard carrying case, 2 Type K probes
TMD90A Dual input digital thermometer w/ triple display
Ideal for HVAC/R technicians, electricians, research, industrial process and quality control
B Measure air velocity or air volume
B Input the surface area for accurate air
flow measurements
B Precise thermistor for temperature
B Continuous moving average results for
up to two hours
TMA10A Anemometer with flexible precision vane
B MIN/MAX/AVG readings
B Air velocity average for eight
multiple points
B Data hold to freeze measurement
display of both readings
B Deluxe hard carrying case
TM45A Type K single input thermometer
Ideal for HVAC/R contractor, plant maintenance, commercial building service
B 0.1 °C (0.1 °F) resolution
B Easy-to-read digital display
B Data Hold to freeze display
B Temperature ranges:
-50 °C to 250 °C
B Protective probe sleeve (TPP1 only)
TPP1-C1 Immersion probe pocket thermometer
TPP2-C1 Flat surface probe pocket thermometer
B Unique, mini-stick design thermometer
B Small, go-anywhere size
B Type K thermocouple compatible
B °C/°F and 1°/0.1° selectable
B Data and max hold
B Type K probe and carrying case included
Air Flow
Ideal for HVAC/R technicians, electricians, research, industrial process and quality control
ACCURACY
(0.1 % rdg + 0.7 °C)
(0.1 % rdg + 0.7 °C)
(0.1 % rdg + 0.7 °C)
(0.3 % rdg + 0.7 °C)
SPECIFICATIONS
Type K
Type J
Type T
Type R & S
Type E
RANGE
-200 °C to 1370 °C
-200 °C to 760 °C
-200 °C to 390 °C
0 °C to 1760 °C
-200 °C to 736 °C (0.3 % rdg + 0.7 °C)
B Accepts Type J, K, T, R, S, E
thermocouple inputs
B RS232 output with optional cable
and software, TM-SWA
For detailed specifications go to www.Amprobe.eu
Relative Humidity
Infrared Thermometer
A quick and effective diagnostic tool for identifying problems in a wide variety of
applications like HVAC/R, fire safety and protection, industrial, maintenance, automotive.
B Laser pointer for easy targeting
B “Pistol grip design” for easy reading
B Display Hold
B Backlit display
IR608A IR Thermometer Laser Pointer
SPECIFICATIONS IR608A IR610A
Range
-18 °C to 400 °C -20 °C to 260 °C
Distance to spot size
8:1 ratio 10:1 ratio
Resolution
N/A 1 °C
Accuracy
± 2 % of reading or ± 2 °C,
whichever is greater
± 3% of rdg or ± 3 °C
Emissivity
Pre-set 0.95 N/A
B Fast response time
B 8:1 Field of view
B Fixed emissivity at 0.95
B Laser pointer for accurate targeting
B Measures to 260 °C front panel switchable
B Narrow 10:1 field of view measures 25 mm at .25 m
distance
B Large 3-1/2 digit display with backlight
IR610A IR Thermometer
B Data Hold, low battery indicator
B Fixed emissivity at 0.95
B Rugged Valox
®
case
B Shipped with carrying case
and batteries
B Dual display
B Relative function monitors humidity and
temperature changes (TH-3)
B Extended probe stem to easily access air ducts
B Capacitive sensor with protective cover
B Min/Max readings
TH-3, THWD-3
Relative Humidity Temperature Meters
B Wet bulb (THWD-3 only)
B Dew point (THWD-3 only)
B Data Hold
B Auto Power off
B Soft Carrying Case
These temperature meters use a precision capacitance sensor to deliver accurate performance
with long term stability. These high accuracy instruments measure the full range of relative
humidity from 0% to 100%
SPECIFICATIONS
TH-3 & THWD-3
%RH Accuracy @ 23 °C
<10, >90 %RH ± 5.0 %RH
10 to 90 %RH ± 3.0 %RH
Temperature coefficient:
0.1x(specified accuracy)/ °C (<23 °C or >23 °C)
Temperature Accuracy
-20 to 60 °C ± 0.8 °C
THWD-3 (only) Wet Bulb & Dew Point
Temperature Accuracy
-20 to 60 °C ± 0.8 °C
ENVIRONMENTAL TESTERS