3332
For detailed specifications go to www.Amprobe.eu
PQ55A
Handheld power analyzer for three-phase power system
measurements
FEATURES PQ55A
Voltage measurement
600 Vrms
Current measurement
Input I1, I2, I3 999.9 A
Input
I4 250 A
Clamp opening
40 mm
Active power (P)
999.9 kW
Apparent power (S)
999.9 kVA
Idle power (Q)
999.9 kVAr
Phase angle (f)
0 ° to 90 °
Frequency measurement
45 to 80 Hz
Harmonics measurement (Using PC)
up to the 31st harmonics
Active power (kWh)
119.3 MWh
Apparent power (kVAh)
119.3 MVAh
Idle power (kvarh)
119.3 Mvarh
Data logger
512 kb, non-volatile memory
Sampling rate
5 s, 30 s, 1 min, 2 min (adjustable)
Safety acc.
EN 61010, CAT III/600 V
Power Quality Recorder
The PQ55A offers real time monitoring, recording and analysis of three phase power systems.
The complete set includes the handheld mainframe, four current clamp adaptors, test leads
with alligator clips, RS232 cable and software CD, large soft carrying case with compartments
and users manual.
ENERGYTEST 2020 E
Handy 3-Phase Power Analyzer
ENERGYTEST 2020 E is a three-phase power analyser and recorder capable of carrying out a
complete analysis of voltages, current and related harmonics, active and reactive powers as well
as active and reactive energies. It also permits to analyse the voltage and current harmonic
components to check and possibly solve all the problems related to the harmonic presence.
B Comprehensive real time monitoring, recording
and analysis of three phase power systems
B True-RMS voltage and current measurement
B Power Factor and phase angle results
B Power Analysis (apparent, active and
reactive power)
B Additional current clamp for neutral line
monitoring
B Internal memory for 99 single
measurement storage
B Opto-isolated RS232 interface for further
analysis and charting
B 50 Hertz operation facilities
Power Quality Analyzers
For detailed specifications go to www.Amprobe.eu
B Energy measurement
B Power measurement
B Harmonics up to 49th
B Incl. 2 MB memory for long self-powering
recording
B Accuracy class 2 according to EN 61036
Safety acc. EN 61010, CAT III/600 V
B Current range 5 mA to 3000 A,
depending on used clamp adapter.
Function Range (V) Resolution (V) Input impedance Overload
protection
Voltage measurement 300, 600 (Autorange) 0.2 300 kOhm 900 V (1 min.)
Current measurement 1 0.001 100 kOhm 5 V
Function PF Resolution
PF measurement 0.2 0.01 digits
0.5 0.01 digits
0.8 0.01 digits
Function Range max. resolution
Harmonic measurement DC - 25. harmonic 0.1 V/0.1 A
26 - 33. harmonic 0.1 V/0.1 A
34 - 50. harmonic 0.1 V/0.1 A
Function Range Resolution
Active power
0 - 999.9 W
1 kW - 999.9 kW
1 MW - 999.9 MW
0.1 W
0.1 kW
0.1 MW
Reactive power
0 - 999.9 VAR
1 kVAR - 999.9 kVAR
1 MVAR - 999.9 MVAR
0.1 VAR
0.1 kVAR
0.1 MVAR
Apparent power
0 - 999.9 VA
1 - 999.9 kVA
1 - 999.9 MVA
0.1 VA
0.1 kVA
0.1 MVA
Active energy
(Class 2 IEC 1036)
0 - 999.9 WH
1 - 999.9 kWH
1 - 999.9 MWH
0.1 WH
0.1 kWH
0.1 MWH
Reactive energy
(Class 3 IEC 1268)
0 - 999.9 VARH
1 - 999.9 kVARH
1 - 999.9 MVARH
0.1 VARH
0.1 kVARH
0.1 MVARH
ENERGYTEST 2020 E is equipped with 2 MB memory. The selected recording rate (5 sec. to 60 min.)
and the amount of selected channels (1-64 signals) determine the maximum recording time.
Example: With an interval of 10 s and 5 selected parameters the max. recording time is 4 days
and 8 hours. With an interval of 1 min. the recording time is 26 days. This includes up to
35 recordings/measurement that can be stored
Voltage and current measurement
PF measurement
Harmonic measurement
Power measurement
Perfect for monitoring computer and power systems as well as:
• Testing of the delivered energy
• Testing of the voltage quality
• Testing and securing a clean operation, e.g. in hospitals or production facilities
Note: only available in English or German language.
POWER QUALITY
Komentarze do niniejszej Instrukcji