GP-2 GeoTest
EN - 21
F
νν - - -- - -
UC UC - - -
If the instrument measures an
interfering voltage higher than 30V
on the amperometric circuit, it does
not perform the test and a screen
similar to the one beside appears.
THIS RESULT CANNOT BE SAVED.
F
νν - - -- - -
230230v - --
If the instrument measures an
interfering voltage higher than 5V
on the voltmetric circuit, it does not
perform the test and a screen similar
to the one beside appears.
THIS RESULT CANNOT BE SAVED.
SAVE
WARNING
UC indicates the presence of too high
voltage on the amperometric circuit.
WARNING
Interfering voltage measured.
SAVE